Technical data

General data and operating conditions

2

l

56

EDKLCFH1134−EER DE/EN 1.0

Operating conditions

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

< 6 months

1K3 (−25 ... +40 °C)

> 6 months
> 2 years: anodise DC bus
capacitors

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−10 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

Site altitude

< 4000 m amsl
Reduce the rated output current by 5%/1000 m above
1000 m amsl.

Pollution

EN 61800−5−1

Degree of pollution 2

Mechanical

Vibration resistance

Germanischer Lloyd

General conditions: acceleration resistant up to 0.7 g

Electrical

Mains connection

Mains system

TT, TN
(earthed neutral)

Unrestricted operation permitted.

IT

Operation not permitted.

Motor connection

Length of the motor
cable

< 20 m (Lenze system cable, shielded)

Cable length for
speed feedback

< 20 m (Lenze system cable, shielded)

Mounting conditions

Mounting location

Wall, mounting plate

Mounting positions

Standard mounting

Vertically suspended, front display

Desk−type mounting

Inclined by maximally 30 ° to the back

Free space

^ 63