Electrical installation, Safety engineering – Lenze ELCAFHIxxx4E34NNER Highline Benutzerhandbuch

Seite 72

Advertising
background image

Electrical installation

Safety engineering

4

l

72

EDKLCFH1134−EER DE/EN 1.0

Detailed features of the safe inputs and the safe output

Terminal

Specification

[Unit]

min.

typ.

max.

I1A, I1B
I2A, I2B
I3A, I3B
I4A, I4B
AIE, AIS

PLC input, IEC−61131−2, 24 V, type 1

Low signal input voltage

V

−3

0

5

Input current at low signal

mA

15

High signal input voltage

V

15

24

30

Input current at high signal

mA

2

15

Input capacitance

nF

3.5

Repetition rate of the test pulses

ms

50

AIE, AIS

Input delay (operating time)

S

0.3

10

CLA, CLB

PLC output, IEC−61131−2, 24 V DC, 50 mA

Low signal output voltage

V

0

0.8

High signal output voltage

V

17

24

29

Output current

mA

60

Cable capacity

nF

100

Cable resistance of a passive sensor

W

200

O1A, O1B

PLC output, IEC−61131−2, 24 V DC

Low signal output voltage

V

0

0.8

High signal output voltage

V

17

24

29

Output current

mA

500

Cable capacity

nF

100

Cable resistance

W

200

Advertising