Electrical installation

Safety engineering

4

l

70

EDKLCFH1134−EER DE/EN 1.0

4.5

Safety engineering

Please observe the following safety instructions and application notes to preserve the
certified safety engineering features and to ensure trouble−free and safe operation.

}

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled restart of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:

ƒ

Safety engineering systems may only be installed and commissioned by
qualified and skilled personnel.

ƒ

All control components (switches, relays, PLC, ...) and the control cabinet
must comply with the requirements of EN 954−1 and ISO 13849−2. This
includes i.a.:
– Switches, relays in IP54 enclosure.
– Control cabinet in IP54 enclosure.
– Please refer to EN 954−1 and ISO 13849−2 for all further requirements.

ƒ

It is essential to use insulated wire end ferrules for wiring.

ƒ

If safety−relevant cables are installed outside the control cabinet, they have
to be protected, e.g. by means of a cable duct:
– Ensure that there are no short circuits.
– For further measures see ISO 13849−2.

ƒ

If an external force acts upon the drive axes, additional brakes are required.
Please observe that hanging loads are subject to the force of gravity!

}

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled restart of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:
Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) > 3 m:

ƒ

It is essential to shield the cable installed between X60 and the connected
components:
– Connect the shield at least to X60 in the connector shell.
– If possible, connect the shield to the connected component as well.

Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) < 3 m:

ƒ

Unshielded wiring is permitted.