DOC,F20,EDN Rev.: -

4.6

Split range setting

To change the range from full range to split range remove the
split range jumper.
This way the positioner can be controlled either by a 4 to 12mA
signal or a 12 to 20mA signal.

The start point can be set at 4 or 12mA with the "ZERO"-
trimmer. The end point (range) can be set at 12 or 20mA with
the "SPAN"-trimmer.

Note:
1. These two adjustments are interrelated, so the zero may

have to be reset after changing the range and vice
versa.

2. To increase the signal turn the trimmer screws clock-

wise (CW). To decrease the signal turn the trimmer
screws counter clockwise (CCW).

20mA

4mA

0mA

Standard setting

0%

100%

20mA

12mA

4mA
0mA

0%

100%

20mA

12mA

4mA
0mA

0%

100%

Split range setting

Setting of second positioner

4.1

4.2

4.3

4.0

Electrical Connections and settings / Elektrische Anschlüsse und Eeinstellungen /

Elektrische aansluitingen en instellingen

Standard setting =

Standard Einstellung =

Standaard instelling

Split range setting =

Einstellung für geteilten Eingangsbereich =

Instellen voor gesplitst bereik

Setting of second positioner =

Einstellung für den zweiten Stellungsregler =

Instelling voor tweede klepstandsteller

Split range jumper =

Jumper für geteilten Eingangsbereich =

Jumper voor gedeeld bereik

Split range jumper