Emerson Process Management El-O-Matic E and P Series E25-E950 Benutzerhandbuch

Seite 55

Advertising
background image

28

DOC,F20,EDN Rev.: -

4. Mount positioner on actuator (see chapter 2 or 3).
5. Make electrical connections as shown in fig. 7.2. Connect

also the control signal of the positioner as decribed in
chapter 4.

Wiring information
Wiring dimension : 1.5 mm 2 / 14 AWG
Tool

: Screwdriver 0.6 x x 3.5 mm

Turning moment

: 0.8 Nm / 7 in/lb

6. Set jumpers to “Direct” or “Reverse” to achieve a 4-20 mA or

a 20-4 mA feedback (see fig. 7.3).

7. Move the actuator pneumatically to the fully closed position.

Adjust the trimmer marked “Zero” to achieve a 4 mA reading
(20 mA in case of "Revers Action").

8. Move the actuator pneumatically to the fully open position.

Adjust the trimmer marked “Span” to achieve a 20 mA
reading (4 mA in case of "Revers Action").

Action "Direct" = 4-20mA at CCW
rotation

Wirkungsweise "Direkt" = 4-20mA bei
CCW Rotation

Werkwijze "Direkt" = 4-20mA bij rota-
tie tegen de klok in

Action "Reverse" = 20-4mA at CCW
rotation

Wirkungsweise "Umgekehrt" = 20-4mA
bei CCW Rotation

Werkwijze "Omgekeert" = 20-4mA bij
rotatie tegem de klok in.

7.0

Position transmitter option PTF20 / Stellungsgeberoption PTF20 / Positietransmitter

optie PTF20

Standard
"Direct" Action

7.2

7.3

-

+

Jumpersetting "Action"

Output signal:
Signal ; 4-20 mA
Voltage : 15-30 VDC

"Zero"
"Span"

"Revers" Action

Valve position

20 mA

4 mA

0 mA

0%

100%

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: