22

DOC,F20,EDN Rev.: -

5.2

Failure Modes - Single Acting (Spring

return)

Spring return actuators may be “fail open” or “fail close”
depending on what happens when the air fails. This air failure
mode must be built into the actuator and maintained when the
actuator is built onto the valve.

In addition both these air failure modes may be either direct
acting or reverse acting depending on what happens at the
positioner when the 4 - 20 mA. signal fails or is reduced to it’s
lowest level.

5.0

Failure Modes / Ausfallarten / Storingen

4. Fail Open - Reverse acting

Input

signal

Rotary

actuator

Linear

actuator

F20

1

2

A

Close

A

3. Fail Close - Reverse acting

Input

signal

Rotary

actuator

Linear

actuator

F20

1

2

A

Close

A

2. Fail Open - Direct acting

Input

signal

Rotary

actuator

Linear

actuator

F20

1

2

A

Close

A

1. Fail Close - Direct acting

Input

signal

Rotary

actuator

Linear

actuator

F20

1

2

A

Close

A

5.3

5.4

5.5

5.6

5.2.1 Changes for Reverse Acting

To change from the standard setup to reverse acting:

1. Change the tubing (see fig. 5.3 to 5.6).
2. Plug the unused actuator port.
2. Remove the cover.
3. Change the action jumper setting by setting both jumpers to

the right side (see fig. 5.2).

4. Replace the cover taking care that the “O” ring seal is in

place and the fixing screws are tightened correctly.

Action

1

2

Air

Signal

Direct

A

Block

Close

Close

Direct

Block

A

Open

Close

Reverse

A

Block

Open

Open

Reverse

Block

A

Close

Open

Air connection

Failure