4pump installation – IMP Pumps NMT(D) LAN (C) 40-100 & NMT SAN LAN (C) flanges Benutzerhandbuch

Seite 24

Advertising
background image

-24-

GB

3.5.2 Power supply
Power supply output is meant for automation elements.

Electrical ratings

Maximum current

100mA

Output voltage

24V ±20%

Output ripple

<1V

• Misconnection or overload could cause pump shutdown or

even permanent damage.

3.5.3 Relay output

Electrical ratings

Rated current

8A

Maximum voltage

250VAC, 25VDC

Maximum load

500VA

3.5.4 Ethernet

Electrical ratings

Connector

RJ-45

Speed

BASE-10, 10Mbit/s

Galvanic insulation

To digital inputs: 1.5kV @1s, 48V permanent

To line voltage: 4kV @1s, 275V permanent

Connection

TCP/IP

Services

http server and client, FTP server

Web language

HTML 1.1

4

Pump installation

4.1

Installation into pipe lines

Pump is protected with a double box during transport. It can be lifted from the

box with internal handles or by lifting it by the heat sink.

Pumps are designed to be built in connecting flanges, using all screws. The

connecting combined flanges are designed so the pump can be installed in

PN6 or PN10 nominal pressure pipelines. Because of the combined flange

design, washers must be used on the pump side, when installing the pump.

For a pump to operate with minimal vibrations and noise it should be installed

into pipe lines with its axis (1-1) in horizontal position, as showed in

figure 1.

Pipes should be without curves for at least 5-10 D (D = rated pipe diameter)

from the flanges.