Rotary actuator – Burkert Type 3501 Benutzerhandbuch
Seite 16

Rotary actuator
14
Fault finding
Problem
Test
Fault
Remedy
Motor does not run
Check connection. Is
– Motor without voltage
– Fix connection
– no humming
voltage applied to
– Power supply not in order
circuit board?
– Thermal circuit
Motor overheated?
breakerhas switched
– Allow motor to cool,
off motor due to
avoid further overloading
overheating.
Are several actuators
– Limit switch welded
– Drive acuators
connected in parallel?
separately or via relay
– Capacitor defective
– Replace capacitor
and limit switch
– Motor humming
Is it possible to turn
– Gear or motor
– Return actuator to
the actuator by
blocked
factory
emergency manualr
operation or only with
great difficulty?
Fuse comes into
Is the drive connected
– Short circuit caused by
– Fix connection
action.
properly? No.
connection fault.
Return actuator to
Resistance of
Winding defective.
factory.
windings outside
tolerance range.
1)
Motor runs on
– Tripping cams do
– Limit switch lug or
– Exchange circuit board
not operate limit switch
block bent
with limit switch block
– Limit switch not
– Limit switch
– Exchange circuit board
working (audibly)
mechanically defective
with limit switch block
– Microswitch operates
– Set tripping cams
too late
according to instructions
Wrong direction of
Compare connections
– Connections
- Connect according to
rotation
with circuit diagram
interchanged
circuit diagram.
(3-position regulator)
Potentiometer
Does the potentiometer
– Defective clutch.
- Replace clutch (if no
doesn't follow
clutch slip? Yes.
success also poten-
the movement
tiometer)
(completely)
Does the potentio-
– Defective potentio-
– Replace potenti-
meteraxis rotate? No.
meter
ometer.
External control
Does the potentio-
– Outer control or
– Fix outer circuit
doesn't work via
meter voltage follow
relay circuit defective
potentiometer
the movement? Yes.
No.
– See "Potentiometer
doesn't follow".
1)
230 V 184–202
Ω 110 V 35,2–38,8 Ω
Resistance measurement on plug 3001-186 from middle contact.