11116552.07 GB/D 06/2010

14

WIKA Operating instructions/Betriebsanleitung E-10, E-11

11116552.07 GB/D 06/2010

15

WIKA Operating instructions/Betriebsanleitung E-10, E-11

Failure

Possible cause

Procedure

Output signal unchanged after change

in pressure

Wrong supply voltage or current spike Replace instrument

Signal span dropping off/too small

Diaphragm is damaged, e.g. through

impact, abrasive/agressive media;

corrosion of diaphragm/pressure

connector; transmission fluid missing.

Contact the manufacturer and replace

the instrument

Signal span too small

Power supply too high/too low

Correct the power supply in line with

the Operating Instructions

Mechanical overload through over-

pressure

Replace instrument

Signal span drops off

Moisture present (e.g. at the cable tail) Install the cable correctly

Signal span erratic

Electromagnetic interference source in

the vicinity, e.g. inverter drive

Shield the device; shield the cables;

remove the interference source.

9. Trouble shooting

GB

In case of unjustified reclamation we charge the reclamation handling expenses.
*) Make sure that after the setting the unit is working properly. In case the error continues to exist send in the instrument for reparation (or

replace the unit).

If the problem persists, contact our sales department.
USA, Canada
If the problem continues, contact WIKA or an authorized agent for assistance. If the pres-
sure transmitter must be returned obtain an RMA (return material authorization) number and
shipping instructions from the place of purchase. Be sure to include detailed information about
the problem. Pressure transmitters received by WIKA without a valid RMA number will not be
accepted.
Process material certificate (Contamination declaration for returned goods)
Purge / clean dismounted instruments before returning them in order to protect our employees
and the environment from any hazard caused by adherent remaining media.
Service of instruments can only take place safely when a Product Return Form has been
submitted and fully filled-in. This Return Form contains information on all materials with which
the instrument has come into contact, either through installation, test purposes, or cleaning.
You can find the Product Return Form on our internet site (www.wika.de / www.wika.com).

10. Storage, disposal / 11. EC declaration of conformity

GB

11. EC declaration of conformity

10. Storage, disposal

When storing or disposing of the pressure transmitter, take precautions with
regard to remaining media in removed pressure transmitters. We recom-
mend cleaning the transmitter properly and carefully. Remaining media in
the pressure port may be hazardous or toxic!

Mount the protection cap when storing the pressure transmitter in order to prevent any
damage to the diaphragm (E-11).

Dispose of instrument components and packaging materials in accordance with the
respective waste treatment and disposal regulations of the region or country to which
the instrument is supplied.

Storage

Disposal

WIKA reserves the right to alter these technical specifications.