Control drawing (fm) d – WIKA WUC-16 Benutzerhandbuch

Seite 44

Advertising
background image

11384850.07 GB/D 06/2014

44

WIKA Operating instructions / Betriebsanleitung, WUC-1x

Hazardous (classified) location

Non-Hazardous location

Non-Incendive installation

Class I, Division 2, Groups A, B, C and D

Class I, Zone 2, Groups IIC

(Note 3)

Series WUC-1X

U+/S+

Non-Incendive transmitter U-/S-

S+

Control equipment

(Note 4), (Note5)

red
black
brown

2-wire system

wire

coding

color

supply + U+/S+

red

supply - U-/S-

black

2-wire system

wire

coding

color

supply + U+

red

supply - U-/S-

black

signal + S+

brown

Non-Incendive parameters:

V

max

= DC 10 ... 30 V, I

max

= 30 mA (Note 2)

Ci = 11 nF (+0.3 nF/m with cable), Li = 10

µH (+2 µH/m with cable)

Notes

1. The non-incendive field wiring concept allows the interconnection of two devices with non-incendive parameters not

specifically examined in combination as a system when: Uo or Voc ≤ V

max

, Ca or Co ≥ Ci + C

cable

, La or Lo ≥ Li + L

cable,

Po ≤ Pi

2. For this current controlled circuit, the parameter I

max

is not required to be aligned with the parameter I

sc

or I

t

of

non-incendive field wiring apparatus.

3. Installation shall be in accordance with the National Electrical Code

®

(ANSI/NFPA70) Sections 504 and 505.

4. The configuration of Control Equipment must be under non-incendive field wiring concept and FM Approved.

5. Control Equipment manufacturer´s installation drawing must be followed when installing this equipment.

6. No revision to this drawing without prior approval by FM.

14. Control drawing (FM)