WIKA operating instructions temperature transmitter, model T24

2370242.09 08/2013 GB/D

4. Design and function

4.1 Description

The analogue temperature transmitter is used for converting a

resistance value into a proportional current signal (4 ... 20 mA). The

analogue signal is transmitted to a series-connected logic unit. For

cable break monitoring the logic unit must be capable of recognising

HI alarms (> 21 mA) and LO alarms (< 3.6 mA).

The electrical components of the transmitter are assembled in

a plastic case and completely encapsulated. Due to the internal

analogue signal processing, this transmitter can also be used in multi-

plexed systems.

The temperature transmitter described in these operating instructions

features a galvanic connection internally between the sensor input

and the analogue output. There must not be any external conductive

connection (e.g. via earth) between the connected sensor and the

analogue output!

4.2 Scope of delivery

Cross-check scope of delivery with the delivery note.

5. Transport, packaging and storage

5.1 Transport

Check the instrument for any damage that may have been caused

during transportation. Obvious damage must be reported immediately.

5.2 Packaging

Do not remove packaging until just before mounting.

Keep the packaging as it will provide optimum protection during

transport (e.g. change in installation site, sending for repair).