WIKA operating instructions temperature transmitter, model T24

2370242.09 08/2013 GB/D

6.2.1 Power supply / 4 ... 20 mA-loop

The T24 is a 2-wire temperature transmitter and depending on the

version, it can be supplied with various types of power supply. Connect

the positive pole of the power supply to the terminal marked with ⊕

and the negative pole of the power supply to the terminal marked with

⊖. With flexible leads we recommend the use of crimped connector

sleeves.

The T24 temperature transmitter requires a minimum terminal voltage

of DC 10 V. The load must not be too high as, otherwise, in the case of

relatively high currents, the terminal voltage at the transmitter will be

too low.

Maximum permissible load depending on the supply voltage:

Load diagram

Load R

A

en Ω

Voltage U

B

en V

Ex ia Ex nL/nA/ic

6.2.2 Connecting the sensor

The connection of a resistance thermometer (e.g. per ICE 60751 or

similar) into a 2-, 3- or 4-wire sensor connection. The sensor input of the

transmitter has to be configured in accordance with the actually used

sensor connection type, otherwise a complete use of the possibilities of

connection compensation is not possible; furthermore this may cause

additional measuring errors (see chapter 6.3 “Configuration”).