WIKA operating instructions attachable indicator model A-IAI-1

18

14016825.01 02/2012 GB/D

Once the cover of the case has been removed, to configure the instrument

continue as follows:

■

To access the menu, while the actual value is displayed, press key 2 for 2

seconds until "dP" appears in the display.

■

To set the parameter values, press keys 2 and 3.

■

To save the set value, press key 1. The parameter name will then appear in

the display once more.

■

To switch to the next parameter, press key 1. The name of the parameter

will appear in the display.

If, during input, no key is pressed for 60 seconds, the configu-

ration of the instrument will be interrupted. Previously-saved

values will not be lost.

Parameters of the A-IAI-1 attachable indicator

Parameters Values

Description

Key 1

Keys 2 and 3

dP

Position of the decimal point (decimal point)
----

Max. indication range: -1999 … 9999

---.-

Max. indication range: -199.9 … 999.9

--.--

Max. indication range: -19.99 … 99.99

-.---

Max. indication range: -1.999 … 9.999

di.Lo

Lower indication range limit (display low)
-1999 ... 9999 This value will be displayed when the input signal

= 4 mA

di.Hi

Upper indication range limit (display high)
-1999 ... 9999 This value will be displayed when the input signal

= 20 mA

Li

Measuring range limit (limit)
oFF

deactivated

Exceeding the measuring range limits is permitted

up to the measuring limit (see note)

on.Er

active, (error display):

The measuring range is limited exactly to the input

signal. When this exceeds or drops below it, a

corresponding error message is displayed.

6. Commissioning, operation