WIKA operating instructions attachable indicator model A-IAI-1

22

14016825.01 02/2012 GB/D

8. Faults

Error

Causes

Measures

Err.2

Measured value

below allowable

range

Input signal too low, or

negative

Current less than 4 mA

Sensor burnout

The error message will reset

itself as soon as the input

signal is once more within

the permissible limits.

Check the transmitter and

the instrument configuration

(e.g. input signal).

Err.3

Indication range

exceeded

Scaling incorrect

The error message will be

reset once the display value

is once more < 9999.

Err.4

Under the indica-

tion range

Scaling incorrect

The error message will reset

itself once the display value

is once more within the

permissible limits.

Err.7

System error

Permissible operating

temperature too high or

too low.

Instrument faulty

Abide by the operating

temperature limits

Replace instrument

Er.11

Value could not be

calculated

Scaling incorrect

Check the setting and the

input signal

CAUTION!

If faults cannot be eliminated by means of the measures listed

above, the attachable indicator must be shut down immedi-

ately, and it must be ensured that signal is no longer present,

and it must be prevented from being inadvertently put back into

service.

In this case, contact the manufacturer.

If a return is needed, follow the instructions given in chapter

9.2 "Returns".