Commissioning, operation – WIKA A-IAI-1 Benutzerhandbuch

Seite 19

Advertising
background image

GB

WIKA operating instructions attachable indicator model A-IAI-1

19

14016825.01 02/2012 GB/D

6. Commissioning, operation

Parameters Values

Description

Key 1

Keys 2 and 3
on.rG

active, (display measuring range limits):

The measuring range is limited exactly to the

input signal. When this exceeds or drops below

it, the indication range limit is displayed. (e.g. for

a humidity of 0 ... 100 % r.H: by dropping below

the limit 0 is displayed, and by exceeding it 100 is

displayed.

When the measuring limits are exceeded (at either end), independ-

ently of the limit settings, the corresponding error message

appears ("Err.1" or "Err.2"). The measuring limits are between

approx. 3.7 and 20.8 mA.

FiLt

Filter (filter)
oFF

Filter deactivated

0.1 ... 2.0

Activate the filter in order to prevent the display

from 'jumping' with every small fluctuation and to

suppress single spikes. The larger the number, the

stronger the filtering.

Offset and slope correction

The offset and slope correction is used to compensate for sensor tolerances

and for the fine adjustment of deviations of the transmitter or signal trans-

ducer.
To set the offset and slope correction, carry out the following:

While the actual value is being displayed, press key 3 for 2 seconds, until

"oFFS" appears in the display.

To set the parameter values, press keys 2 and 3.

To save the set value, press key 1. The parameter name will then appear in

the display once more.

To switch to the next parameter, press key 1. The name of the parameter

will appear in the display.

Parameters Values

Description

Key 1

Keys 2 and 3

oFFS

Zero offset (offset)
-5.00 … 5.00 The input of the offset is made in digits. The set

offset value is subtracted from the measured value.