Safety – WIKA A-IAI-1 Benutzerhandbuch

Seite 7

Advertising
background image

GB

WIKA operating instructions attachable indicator model A-IAI-1

7

14016825.01 02/2012 GB/D

2. Safety

Skilled electrical personnel

Skilled electrical personnel are understood to be personnel who, based on

their technical training, know-how and experience as well as their knowledge

of country-specific regulations, current standards and directives, are capable

of carrying out work on electrical systems and independently recognising

and avoiding potential hazards.

The skilled electrical personnel have been specifically trained for the work

environment they are working in and know the relevant standards and regula-

tions.

The skilled electrical personnel must comply with current legal accident

prevention regulations.

2.3 Additional safety instructions for instruments per ATEX

WARNING!

Non-observance of these instructions and their contents may

result in the loss of explosion protection.

Electrical specifications in accordance with the EC-type examination

certificate.
Input circuit:

In intrinsically-safe ignition protection type Ex ia/ib IIC/IIB.

Only for connection to certified intrinsically-safe circuits.

Maximum values:

U

i

= 28 V

I

i

= 100 mA

P

i

= 1,200 mW

Maximum effective internal capacitance C

i

< 13 nF

The maximum effective internal inductance is negligibly small.

WARNING!

Special conditions for all variants:

1. Modifications or repairs of the device may not be performed

by the customer. For maintenance or repair the device must

be sent to the manufacturer.

2. The opening of the device is only permitted outside the

hazardous area.

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: