WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

7. Semiconductor switches such as thyristors, triacs or SSRs generate

interference voltages due to their non-linear characteristics and their

finite gate trigger voltage. This also protects them against surges due

to their limited reverse voltage. Here, varistors, RC filters or chokes

are often used. If possible, for semiconductor switches the use of

zero-voltage switches is recommended.

8. Use a line filter for mains voltage to controllers, where the mains

supplies are very noisy. Fit the filter as close as possible to the

controller and connect with short lines, safe from touch. The filter

absolutely must be connected to a protective earth. Note that a small

reactive current flows to ground.

The supply of the loads connected through the controller must not be

tapped on the controller side after the mains filter.

7. Configuration

SOFTWARE .10

Setting options

Key: UP

By pressing this key, the parameter or the parameter value is

increased.
Key: DOWN

By pressing this key, the parameter or the parameter value is

reduced. On an alarm, the buzzer function is switched off by

pressing this key.
Key: SET

While this key is pressed, the set point will be displayed.

This key is also used for parameter setting.

6. Commissioning, operation / 7. Configuration