18

WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

Function as limit alarm

If the actual value is outside the set

temperature limits; thus above the

upper limit value or below the lower

limit value, the alarm contact will

be active.

Function as band alarm

Inverse switching behaviour as with

limit alarms. Light 3 indicates or the

alarm contact is energised if the

actual value is within the set limits.

P6: Actual value correction

The value set here is added to the sensor‘s measured value. The

modified measurement is shown on the display and serves as the basis

for control.
P19: Key lock

The key lock enables the operator keys to be blocked. In the locked state,

changing the set point via the keys is not possible. When you attempt

to adjust the set point while the key lock is active, the message "---"

appears on the display.
P30: Lower alarm limit
P31: Upper alarm limit

The alarm output with single-sided hysteresis (see parameter P32) is

effectively a limit or band alarm. The limit values, with limit as well as

band alarm, can at any time be relative, and thus concurrent with the set

point S1/S1', or absolute, so independent of the set point S1/S1'. The

hysteresis acts on one side inwards with limit alarms, and outwards with

band alarms.

7. Configuration

P32: Hysteresis alarm, single-sided

The hysteresis is applied on a single-side of the set limit value. It is active

depending on the alarm definition.

Upper limit

Set point

Alarm

T

Lower limit

Upper limit

Set point

Alarm

T

Lower limit

Alarm