Faults, Maintenance and cleaning / 9. faults – WIKA SC64 Benutzerhandbuch

Seite 24

Advertising
background image

24

WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

Electrical connections must not come into contact with

moisture.

Residual media in the dismounted instrument can result

in a risk to persons, the environment and equipment. Take

sufficient precautionary measures.

For information on returning the instrument see chapter

10.2 "Return".

9. Faults

Status messages

Display Causes

Measures

F1L

Sensor error, short circuit

Check sensor

F1H

Sensor error, sensor burnout Check sensor

F3L

Limit alarm (actual value

> P30)

see parameters P30, P31, P32,

A30, A31

F3H

Limit alarm

(actual value > P31)

see parameters P30, P31, P32,

A30, A31

F3

Band alarm

(P30 < actual value < P31)

see parameters P30, P31, P32,

A30, A31

_ _ _

Key lock active

see parameter P19 or A19

Flashing

display

Temperature alarm

(see A31)

The alarm can be cancelled

with the DOWN key.

EP

Data loss in parameter

memory (Control contact 1

is de-energised)

If the error cannot be eliminated

by powering down and then up,

the controller must be repaired.

When A31 = 4, sensor error messages are stored and are displayed,

even once the cause of the error has been cleared. By acknowledging

with the DOWN key, the error message will be deleted.