WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

Para-

meters

Functional

description

Setting range

Standard

setting

A1

Switching mode K1

0: Heating contact

1: Cooling contact

2: Alarm function

3: Alarm function inverted

0

A3

Function on sensor error

0: Off when error

1: On when error

0

A8

Display mode

(Parameter is displayed

with a resolution of 0.1 °C)

0: Integer

1: resolution 0.5 °C

2: resolution 0.1 °C

1

A19

Parameter lock

0: no lock

1: A-parameter locked

2: A-/P-parameter locked

0

A30

Type of alarm function

0: Limit alarm, relative

1: Limit alarm, absolute

2: Band alarm, relative

3: Band alarm, absolute

0

A31

Special function for alarm 0: not active

1: Display flashes

3: Error display (F3.),

display flashes

4: as 3, save

0

A32

Type of display

0: Actual value display

1: Set-point display

0

A40

Hysteresis mode with

heating or cooling function

0: symmetric

1: one side

1

A50

Minimum action time,

control contact "On"

0 ... 999 sec.

0 sec.

A51

Minimum action time,

control contact "Off"

0 ... 999 sec.

0 sec.

A54

Control contact delay after

"Power on"

0 ... 999 sec.

0 sec.

A56

Alarm suppression time

after "control ON" or set-

point change

0 ... 60 min.

20 min.

A60

Sensor selection

11: Pt100

21: PTC – 2-wire

22: Pt1000 – 2-wire

11