A30: Type of alarm function

The alarm output evaluates an upper and a lower limit value (see

parameters P30 and P31). Here you can select whether the alarm is

active when the temperature is between these two limits, or if the alarm

is given when the temperature is outside of them. On sensor error, the

alarm is activated regardless of this setting. The output can also be

inverted with parameter A1, so that it functions like a release.

A31: Special functions for alarm

Here it is selectable whether the the display should flash. The alarm can

be cancelled with the DOWN key.

A32: Display of actual value or set point

With this parameter, it can be defined whether the actual value or the set

point should be displayed in the normal state.

A40: Hysteresis mode, control contact

With this parameter it can be chosen whether the hysteresis at the

respective switching point is symmetrical or single-sided. With hysteresis

programmed as single-sided, for heating mode it is set below and for

cooling mode above the set point; with symmetrical hysteresis there is

no difference.

A50: Minimum action time, control contact "On"

A51: Minimum action time, control contact "Off"

These parameters permit a delay in switching the respective output

contact on or off in order to reduce the switching frequency. The set time

dictates the full minimum duration of the switching-on or switching-off

phase. This time is also effective when configured as an alarm contact.

A54: Control contact delay after "Power on"

This parameter enables the delayed switching on of the control contact

after turning the power supply on. Thus, overloading the power network

by simultaneously turning on many loads is avoided.