WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

d3

Defrost time limit

0 ... 99 min.

0 = without time limit

30 min.

* Standard setting dependent on sensor type

Parameter description

P2: Hysteresis, control contact 1

The hysteresis can be arranged either symmetrically or on only one side

of the set point (see A40).

For single-sided setting the hysteresis is effective below for a heating

contact, above for a cooling contact. With symmetrical hysteresis, in both

cases it is effective evenly above and below the switchpoint by a value of

half the hysteresis (see drawings).

7. Configuration

P4: Lower set-point limit
P5: Upper set-point limit

The adjustment of the set point can be limited upwards and downwards.

This prevents the end-user of a system setting inadmissible or dangerous

set points.

Set point

T

hysteresis

ON

ON

OFF

OFF

t

Relay contact

Set point

T

hysteresis

ON

ON

OFF

OFF

t

Relay contact

Heating controller,

single-sided hysteresis

Cooling controller,

symmetrical hysteresis