2 Installation
2.1
Regulations and notes
2.2
Electrical connection
Connections must be made in accordance with the connection diagram
(label).
Switching action
with n.o. (make)
contact
The difference in the current drawn between the activated and the inactivated
oscillator is used to operate a switching amplifier which, in turn, converts the
input signal into a logic output signal.
Nominal voltage
8 V DC (Ri
1k)
Operating
voltage
5 — 25 V
Current drawn
3 mA (active area free)
1 mA (active area damped)
Secondary
switch devices
Intrinsic safety to II 2 G EEx ia IIC T6 is only assured in conjunction with the
transistor relay, type KFA6-SR2-Ex...W (II(1) G D [EEx ia] IIC) from
Pepperl & Fuchs, www.pepperlfuchs.de.
V
The electrical connection must only be carried out by properly qualified
personnel.
Control flag outside
sensor gap
Relay energized
Active area free
Oscillator activated
Current drawn
3 mA
Control flag inside
sensor gap
Relay de-energized
Active area damped
Oscillator off
Current drawn
1 mA