12

4 Functions and operation

You can operate the transmitter by using the “Span” and “Zero”
push-buttons in conjunction with the blink cycles of the “Power”
and “Status” LEDs that have already been described in Chapter 3
“Displays and controls”.

In use, two operating states can be distinguished:

- Operating level (normal operation)

- Parameter level (programming mode)

Operating level

The transmitter is at the operating level two seconds after power-
on, or after leaving the parameter level.

Parameter level

You can access the parameter level by simultaneously pressing the
push-buttons “Span” and “Zero” (for at least 5 seconds). The fol-
lowing functions can be programmed at this level:

- Limit value for limit comparator 1

- Limit value for limit comparator 2

- Fine calibration (zero point)

- Fine calibration (full scale)

- Teach-in

The parameter level is exited (quit) after editing the “Teach-in” pa-
rameter, or if no push-button has been pressed for at least 20 sec-
onds.

The individual parameters can be altered, one after another. You
can move from parameter to parameter by simultaneously pressing
the two push-buttons “Span” and “Zero” for less than 1 second.