4 Functions and operation

Teach-in

The “Teach-in” parameter serves to define the 0 % value.

During programming, the zero point (e.g. 4mA) is produced at the
output. This value is accepted by pressing the “Zero” push-button
(“Zero” only, not together with “Span”). After a time-out without ac-
ceptance, the old value will be available again.

Example:

The position of a valve is detected by a potentiometer. The potenti-
ometer covers the range 50 to 150

Ω

, with 50

Ω

corresponding to the

valve closed. The range is programmed as follows:

- Potentiometer 50 — 150

Ω

- Output 0 — 20mA

However, because of mechanical tolerances, the potentiometer po-
sition is 52

Ω

with the valve closed, which results in an output cur-

rent of 0.4mA. Thanks to the “Teach-in” function, this error can be
eliminated as described below:

- Close valve

- Call parameter level and select “Teach-in”

(0.4mA should then be present at the output).

- Press the “Zero” push-button – the output must now

change to 0mA.

- Confirm alteration by simultaneously pressing the

“Span” and “Zero” push-buttons.

- Exit the parameter level (either after a time-out of 20sec, or by

pressing “Span and Zero“ again).