Electrical installation

Connection plan

Drive controller type 712 for mains connection 190 ... 265 V

5

58

EDB712 DE/EN 2.1

5.3.2

Drive controller type 712 for mains connection 190 ... 265 V

Note!

The drive controller 712 is set in the factory for operation with

340 ... 460 V. For operation with 190 ... 265 V a soldered jumper

must be changed and three 220 kΩ/0.5 W resistors soldered in

positions R101, R102 and R103.

Danger!

Only appropriately skilled personnel are allowed to make the

modification for operation on 190...265 V.

240 V

400 V

712_003

Fig. 4

Modification of the drive controller 712 for 190 ... 265 V mains connection by changing

soldered jumpers

1. Remove protective cover over the device printed circuit board, if

necessary.

2. Move the soldered jumper from the soldering terminal ”400 V” to the

soldering terminal ”240 V” by soldering.