Electrical installation
Connection plan
Expansion of the torque setting range
5
62
EDB712 DE/EN 2.1
5.3.4
Expansion of the torque setting range
As supplied the device is setup for operation without a neutral conductor. In this
case the torque setting range is approx. 1:20.
If a larger setting range is required, two measures must be taken:
ƒ
Connect the neutral conductor to the motor star point
ƒ
Replace the resistor on soldering terminals (position R420, fitted with
22 kΩ resistor from the factory) with a 100 kΩ resistor.
712_006
Fig. 8
Replacing the 22k
Ω
resistor with a 100 k
Ω
resistor at position R420