3. inTended use

Unauthorized use of the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection can be
dangerous to people, nearby equipment and the
environment.

The device is designed as a valve and sensor connec-

•

tion. Only sensors and valves may be connected which

comply with the technical specifications.
During use observe the authorized data, the opera-

•

ting conditions and conditions of use specified in the

contract documents and operating instructions, as

indicated in the EC-Type Examination Certificate (see

Appendix of the Operating Instructions).
The device may be used only in conjunction with third-

•

party devices and components recommended and

authorized by Bürkert.
Correct transportation, correct storage and installation

•

and careful use and maintenance are essential for

reliable and faultless operation.
Use the device only as intended.

•

english

5

explosion protection approval

3.1.

Any unauthorized changes to the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection or to components
invalidate the explosion protection approval.

Predictable misuse

3.2.

Do not subject the housing of the Power I/O Box Type 8643
to mechanical loads (e.g. by placing objects on it or standing
on it).

english

6

4. basic safeTy

insTrucTions

These safety instructions do not make allowance for any:

contingencies and events which may arise during the instal-

•

lation, operation and maintenance of the devices.
local safety regulations – the operator is responsible for

•

observing these regulations, also with reference to the
installation personnel.

Hazardous if used in explosion-risk area. Risk of
explosion from electrical voltage!
The Power I/O Box Type 8643 is designed as ignition
protection type Ex-e (increased safety).

Before working on non-intrinsically safe circuits of

•

the Power I/O Box Type 8643, always switch off the

operating voltage of the system!

Danger of explosion due to internal charging of the
Power I/O Box Type 8643!
When the power supply to the Power I/O Box Type
8643 is switched off, the internally stored charge will not
be completely dissipated for 4 minutes. To prevent an
explosion, switch off the power supply before connecting
or disconnecting Ex-e terminals.

english

7

Do not remove the cover from the connection terminals

•

for Ex-e switching circuits until the connected Ex-e cir-

cuits have been disconnected from the power supply

for longer than 4 minutes.
If using the 2-wire version in potentially explosive

•

areas, do not connect any cable to the Power 24 V

supply terminals!

Danger of explosion if the allowable ambient tempe-
rature ranges are exceeded!

Observe the respective ambient temperature range

•

which is based on the type designation (e.g. 8643-2-

AL-KS-F-I/O), according to the table in the EC-Type

Examination Certificate (see Appendix of the Opera-

ting Instructions / Type Examination Certificate).

Danger of explosion due to unauthorized combi-
nation of the ignition protection types!
Due to unauthorized combination of the ignition pro-
tection types, the device is not suitable for use in the
explosion-risk area. If the device is nevertheless used in
this area, there is a danger of explosion!

If the bus supply of the 4-wire version of the device

•

was operated once in ignition protection type of

increased safety (e), the bus supply may no longer be

intrinsically safe in the ignition protection type (i).