4
3. inTended use
Unauthorized use of the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection can be
dangerous to people, nearby equipment and the
environment.
The device is designed as a valve and sensor connec-
•
tion. Only sensors and valves may be connected which
comply with the technical specifications.
During use observe the authorized data, the opera-
•
ting conditions and conditions of use specified in the
contract documents and operating instructions, as
indicated in the EC-Type Examination Certificate (see
Appendix of the Operating Instructions).
The device may be used only in conjunction with third-
•
party devices and components recommended and
authorized by Bürkert.
Correct transportation, correct storage and installation
•
and careful use and maintenance are essential for
reliable and faultless operation.
Use the device only as intended.
•
english
5
explosion protection approval
3.1.
Any unauthorized changes to the Power I/O Box Type 8643
with FOUNDATION Fieldbus connection or to components
invalidate the explosion protection approval.
Predictable misuse
3.2.
Do not subject the housing of the Power I/O Box Type 8643
to mechanical loads (e.g. by placing objects on it or standing
on it).
english
6
4. basic safeTy
insTrucTions
These safety instructions do not make allowance for any:
contingencies and events which may arise during the instal-
•
lation, operation and maintenance of the devices.
local safety regulations – the operator is responsible for
•
observing these regulations, also with reference to the
installation personnel.
Hazardous if used in explosion-risk area. Risk of
explosion from electrical voltage!
The Power I/O Box Type 8643 is designed as ignition
protection type Ex-e (increased safety).
Before working on non-intrinsically safe circuits of
•
the Power I/O Box Type 8643, always switch off the
operating voltage of the system!
Danger of explosion due to internal charging of the
Power I/O Box Type 8643!
When the power supply to the Power I/O Box Type
8643 is switched off, the internally stored charge will not
be completely dissipated for 4 minutes. To prevent an
explosion, switch off the power supply before connecting
or disconnecting Ex-e terminals.
english
7
Do not remove the cover from the connection terminals
•
for Ex-e switching circuits until the connected Ex-e cir-
cuits have been disconnected from the power supply
for longer than 4 minutes.
If using the 2-wire version in potentially explosive
•
areas, do not connect any cable to the Power 24 V
supply terminals!
Danger of explosion if the allowable ambient tempe-
rature ranges are exceeded!
Observe the respective ambient temperature range
•
which is based on the type designation (e.g. 8643-2-
AL-KS-F-I/O), according to the table in the EC-Type
Examination Certificate (see Appendix of the Opera-
ting Instructions / Type Examination Certificate).
Danger of explosion due to unauthorized combi-
nation of the ignition protection types!
Due to unauthorized combination of the ignition pro-
tection types, the device is not suitable for use in the
explosion-risk area. If the device is nevertheless used in
this area, there is a danger of explosion!
If the bus supply of the 4-wire version of the device
•
was operated once in ignition protection type of
increased safety (e), the bus supply may no longer be
intrinsically safe in the ignition protection type (i).
english