Seite 5

16
Cable gland for earth cable PA
(potential equalisation)
Cable glands for intrinsically safe
circuits (8 screw joints, blue)
Cable glands for bus and power
supply (4 screw joints, black)
Location of the cable connections on the plastic
Fig. 2:
housing of the device
english
17
When delivered, the cable glands are covered
with protective caps. These protective caps must
remain on the cable glands until the cables are
connected to keep out dirt.
diP-switch
6.2.2.
ON
ON
OFF
Switch 1
DIP-Switch
Fig. 3:
Switch 1 - ON:
Simulate can be locked so that the READBACK_D is over-
written in the DO_valve function block.
english
18
led-display
6.2.3.
LED 1 green
LED 2
green
LED 3 red
LED-Module
(optional)
LED 1
is lit when voltage is applied to the bus
supply.
LED 2
is lit if the device is using cyclic data transfer.
LED 3
is lit if the device is not using cyclic data
transfer (only after Power on or if the
Watchdog is active).
Location of the LED-Display
Bild 1:
If neither LED 2 nor LED 3 is lit, check power
supply!
english
19
Technical daTa
7.
General Technical data
7.1.
Values for 2 and 4-lead versions
Housing material
Polyester, aluminium
Cable entry
Polyamide cable fittings
Degree of protection
IP65 (DIN EN 60529)
Protection class
3 (DIN EN 61140(VDE 0140-1))
Ignition protection identi-
fication (entire device)
II 2 (1) G Ex [ia] me IIC T
Inputs
8, intrinsically safe, NAMUR
(according to EN 60947-5-6)
Outputs
4, intrinsically safe
Outputs for pilot valves:
Min. switching current
30 mA (Power reduction on
holding current after min. 50 ms)
Min. holding current
15 mA
Internal resistance
330 Ohm
Open-circuit voltage
24 V
english
Type 8643