Adjustment of transmitter – WIKA T19 Benutzerhandbuch

Seite 12

Advertising
background image

12

2143014.05 06/2014 GB/D

GB

WIKA operating instructions temperature transmitter, model T19

7.1 Preparation

Connect a suitable simulation source to the input of the T19 (Pt100).

When simulating a Pt100 connect the simulator in a 3-wire connecting

circuit. We recommend the use of passive resistances. Electronical

simulation sources can cause incorrect measurement values.

Connect a mA meter in 4 ... 20 mA-loop according to section 5 (with

R

i

≤ max. permissible load!) to measure the output signal.

Connect a suitable power supply to the transmitter.

7.2 Adjustment

Carry out steps

through

in the order given.

Set the lower value of the measurement range with the simulator, e.g.

-30 °C for measurement range -30 ... +50 °C.

Turn the zero potentiometer Z, until the output signal shows the

desired value.

Set the end value of the measurement range with the simulator, e.g.

+50 °C for measurement range -30 ... +50 °C.

Turn the span potentiometer S, until the output signal shows the

desired value.

High output currents (for example 20 mA) should therefore not exist

longer than 1 minute (in total) when doing adjustment. If adjustment

has to be repeated then allow the transmitter to cool down for approx.

20 minutes (disconnect the transmitter from the power supply).

Repeat step

and check output signal of zero point.

Repeat step

and check output signal of span.

7.3 Closing steps

Disconnect the simulator, the mA meter, and the power supply.

7. Adjustment of transmitter