Mounting / 5. electrical connections, Electrical connections – WIKA T19 Benutzerhandbuch

Seite 9

Advertising
background image

9

2143014.05 06/2014 GB/D

GB

WIKA operating instructions temperature transmitter, model T19

4.2 Mounting for rail mounting version

The transmitters for rail mounting (model T19.30) are designed for

mounting on a standard rail or for wall mounting.

Rail mounting

The transmitter is affixed without the use of auxiliary parts by sliding

onto a 35 mm top hat rail (DIN EN 50022-35).

Demounting is done by freeing the snap parts.

Wall mounting

Lever the snap parts outwards with a screwdriver until they lock into

place. Mount case to the wall by means of two screws.

5. Electrical connections

In the case of the transmitters described here there is an

internal galvanic connection between the sensor input and

analogue output.
No external conducting is to be made (for example, by

earthing) between the connected temperature sensor and

analogue output!
We recommend the use of crimped connector sleeves in the

case of flexible leads.
For model T19.30 the connection cable of a temperature

probe must be shielded and grounded.

To connect a Pt100 sensor in a 2-wire connecting circuit:

Set a jumper between the input terminals 2 and 3 in accordance with

section 5.1.!

4. Mounting / 5. Electrical connections