Specifications – WIKA TR30 Benutzerhandbuch

Seite 11

Advertising
background image

GB

WIKA operating instructions model TR30

11377551.06 07/2014 GB/D

11

Analogue output

4 ... 20 mA, 2-wire

Measuring error per

DIN EN 60770, 23 °C ±5 K

0.2 % (Transmitter)

3)

Linearisation

Linear with temperature per DIN EN 60751

Linearisation error

±0.1 %

4)

Switch-on delay, electrical

< 10 ms

Signalling of sensor burnout

Configurable: NAMUR downscale < 3.6 mA

(typically 3 mA)

NAMUR upscale > 21.0 mA (typically 23 mA)

Sensor short-circuit

Not configurable, generally NAMUR downscale

< 3.6 mA (typ. 3 mA)

Load R

A

R

A

≤ (U

B

- 9 V) / 0.023 A with R

A

in Ω and U

B

in V

Effect of load

±0.05 % / 100 Ω

Power supply U

B

DC 10 ... 35 V

Max. permissible residual

ripple

10 % at 24 V / maximum 300 Ω Load

Power supply input

Protected against reverse polarity

Power supply effect

±0.025 % / V

Electromagnetic compatibility

(EMC)

2004/108/EC, DIN EN 61326 emission

(Group 1, Class B) and immunity (industrial

application)

5)

, and also per NAMUR NE21

Temperature units

Configurable °C, °F, K

Info data

TAG No., descriptor and message can be stored

in transmitter

Configuration and calibration

data

Permanently stored in EEPROM

Electrical connection

M12 x 1 circular connector, 4-pin

Angular DIN connector Form A for cable with

Ø 6 ... 8 mm, cross section max. 1.5 mm²

Readings in % refer to the measuring span

For a correct determination of the overall measuring error, both sensor and

transmitter measuring deviations have to be considered.

1) For detailed specifications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.

2) The temperature transmitter should therefore be protected from temperatures over 85 °C

3) For measuring spans smaller than 50 K additional 0.1 K

4) ±0.2 % for measuring ranges with a lower limit less than 0 °C

5) Use resistance thermometers with shielded cable, and ground the shield on at least one end of

the lead, if the cables are longer than 30 m or leave the building.

3. Specifications