Specifications – WIKA TR30 Benutzerhandbuch

Seite 12

Advertising
background image

GB

12

WIKA operating instructions model TR30

11377551.06 07/2014 GB/D

Voltage U

B

in V

Load R

A

in

Ω

0

10

24 30 36

1182

909
636

Load diagram

For setting the measuring range see chapter 7 “Configuration

model TR30-W”.

Output signal 0 ... 10 V, model TR30-V

Measuring element and measuring insert

The Pt100 measuring element is located in the thermometer‘s probe tip.

The 0 … 10 V transmitter is mounted in the tubular body of the

thermometer.

Output signal 0 ... 10 V, model TR30-V

Temperature range

Measuring range without neck tube

-50 ... +150 °C, with neck tube -50 ... +200 °C

2)

,

measuring ranges are not adjustable

Measuring element

Pt100 (measuring current: 0.5 mA)

Sensor tolerance value

1)

per DIN EN 60751

Class B

Measuring span

minimum 50 K, maximum 250 K

Basic configuration

Measuring range 0 ... 100 °C

Measuring ranges

-50 ... +50, 0 ... 50, 0 ... 80, 0 ... 100, 0 ... 120,

0 ... 150, 0 ... 200 °C

Analogue output

0 ... 10 V, 3-wire

Overall measuring error

3)

< 0.5 % of span

Power supply U

B

DC 12 ... 30 V

Max. permissible residual ripple 10 %

The permissible load

depends on the loop

supply voltage.

3. Specifications