Commissioning, operation – WIKA TR31 Benutzerhandbuch

Seite 18

Advertising
background image

GB

14096788.01 07/2014 GB/D

18

WIKA operating instructions models TR31-3, TR31-K

6. Commissioning, operation

WARNING!

Avoid putting any mechanical loading on the electrical

connections and on the enclosures. Connections must only

be opened once the instrument has been depressurised and

has cooled down.
Maximum permissible temperatures:

Without neck tube: -50 … +150 °C (-58 ... +302 °F)

With neck tube: -50 … +250 °C (-58 ... +482 °F)

1)

At case with transmitter: 85 °C (185 °F)

With directly connected cable: -20 ... +80 °C (-4 ... +176 °F)

1) Version with mineral-insulated sheathed cable can be used up to 300 °C (572 °F).

6.1 Mounting

These resistance thermometers are designed for screw-fitting directly

into the process. The insertion length, along with the flow velocity and

viscosity of the process media, may reduce the max. loading on the

thermowell.

The housing must be grounded against electromagnetic fields and

electrostatic discharge. It is not necessary to connect the housing

separately to the equipotential bonding system, provided that it has a

fixed and secure contact to the metallic vessel, its components or pipes,

and that these are connected to the equipotential bonding system.

When there is a non-metallic contact with the vessel, or with its

structural components or piping, the instrument must be provided with

equipotential bonding.

WARNING!

Neither repairs nor structural modifications are permitted,

and any would void the guarantee.