WIKA operating instructions models TR31-3, TR31-K
7. Configuration
The measuring range is configurable between -50 ... +250 °C
(-58 ... +482 °F). The configuration software checks the required
measuring range and will only accept permissible values. Intermediate
values are configurable; the smallest increment is 0.1 °C or 0.1 °F.
The
thermometers are delivered configured to customer specifications within
the configurable limits.
Please note:
The measuring range of the thermometer is limited by the application
range of the measuring element, not by the setting range of the
transmitter.
Maximum permissible temperatures:
■
Without neck tube: -50 … +150 °C (-58 ... +302 °F)
■
With neck tube: -50 … +250 °C (-58 ... +482 °F)
1)
■
At case with transmitter: 85 °C (185 °F)
■
With directly connected cable: -20 ... +80 °C (-4 ... +176 °F)
1) Version with mineral-insulated sheathed cable can be used up to 300 °C (572 °F).