Current signal for fault signal

configurable in accordance with

NAMUR NE43

downscale < 3.6 mA (typically 3.5 mA)

upscale > 21.0 mA (typically 21.5 mA)

Sensor short-circuit

not configurable, in accordance with

NAMUR NE43 downscale < 3.6 mA

(typically 3.5 mA)

Sensor current

< 0.3 mA (Self-heating can be neglec-

ted.)

Load R

A

R

A

≤ (U

B

- 10 V) / 23 mA with R

A

in Ω

and U

B

in V

Effect of load

±0.05 % / 100 Ω

Power supply U

B

DC 10 ... 30 V

Max. permissible residual ripple 10 % generated by U

B

< 3 % ripple of

the output current

Power supply input

protected against reverse polarity

Power supply effect (depending

on the power supply)

±0.025 % / V

Electromagnetic compatibility

(EMC)

2004/108/EC, EN 61326 emission

(group 1, class B)

3)

, and interference

immunity (industrial application),

configuration at 20 % of the full

measuring range

Temperature units

configurable °C, °F, K

Info data

TAG No., descriptor and user message

can be stored in transmitter

Configuration and calibration

data

permanently stored

Electrical connection

M12 x 1, 4-pin circular connector

Readings in % refer to the measuring span

For a correct determination of the overall measuring deviation, both sensor and transmitter measu-

ring deviations have to be considered.

1) The temperature transmitter should therefore be protected from temperatures over 85 °C

(185 °F).

2) ±0.2 % for measuring ranges with a lower limit less than 0 °C (32 °F)

3) Use resistance thermometers with shielded cable and ground the shield at at least one end

of the lead if the lines are longer than 30 m or leave the building. Operate the instrument in a

grounded state.