8 Functions and operation
Fault output
The "fault output" function can only be activated through the setup
program. If the "fault output" function is active, the following faults
will be monitored:
- probe break
- probe short-circuit (RTD only)
- overrange
- underrange
- internal faults (Pt100 of cold junction is faulty, ...)
If any of these events occur, the blink response for overrange will be
activated.
v
see “Illumination/blink behavior” on page 16.
H
The limits (limit comparators) are indicated only via the
status and power LEDs.
Unlike the transmitters 707021/... (PCP) and 707022/...
(LCD), the open-collector outputs are not available on type
707025/... (Ex).