8 Functions and operation

Teach-in

The “Teach-in” parameter serves to define the 0 % value.

During programming the zero point is produced at the output (e.g.
4mA). This value is accepted by pressing the “Zero” button (“Zero”
only, not together with “Span”). After a time-out without
acceptance, the old value will be available again.

Example:

The position of a valve is detected by a potentiometer. The
potentiometer covers the range 50 to 150

, with 50

corresponding to the valve closed. The range is programmed as
follows:

- potentiometer 50 — 150

- output 0 — 20mA

However, because of mechanical tolerances, the potentiometer
position is 52

 with the valve closed, thus resulting in an output

current of 0.4mA. Thanks to the “teach-in” function, this error can
be eliminated as follows:

- close valve

- call parameter level and select “Teach-in”

(0.4mA should then be present at the output).

- press the “Zero” button – the output

must now change to 0mA.

- confirm alteration by simultaneously

pressing the “Span” and “Zero” buttons.

- exit the parameter level (either after a time-out of 20sec, or by

pressing “Span” and “Zero” again).