1 connection with the automation system, Connection with the automation system, Driveserver – Lenze DriveServer Erste Schritte Benutzerhandbuch
Seite 42

DriveServer
L
40
DriveServer DE/EN 1.1
3.1
Connection with the automation system
The communication with the target system (controller, Drive PLC, etc.) requires a fieldbus-specific
interface module for the PC and the corresponding fieldbus modules for the drives to be connected.
The following table gives an overview of the transfer media which are included in the basic DriveServer
package.
Bus system
PC port
Max. number
of
automation
systems
Required
hardware components
Required
software components
System bus
(CANopen)
Parallel port
(LPT port)
63
PC system bus adapter 2173
incl. connection cable and
voltage supply adapter
•
for DIN keyboard connection
(EMF2173IB)
•
for PS/2 keyboard connection
(EMF2173IBV002)
•
for PS/2 keyboard connection
with electrical isolation
(EMF2173IBV003)
Bus server for system bus
(part of the DriveServer
package)
USB
( Universal
Serial Bus)
PC system bus adapter 2177
incl. connection cable
(EMF2177IB)
LECOM
Serial port
(COM port)
1
(RS232)
•
Fieldbus module EMF 2102IB
V001 or V004
Bus server for LECOM
(part of the DriveServer
(COM port)
(RS232)
V001 or V004
•
PC system cable RS232/485,
5m (EWL0020)
(part of the DriveServer
package)
31
(RS485)
•
Fieldbus module EMF 2102IB
V001
•
PC system cable RS232/485,
5m (EWL0020)
•
Interface converter
RS232/RS485 with automatic
change of direction*
52
(optical fibre)
•
Fieldbus module EMF 2102IB
V003
•
Optical fibre adapter
(EMF2125IB)
•
Power supply for adapter
(EJ0013)
•
Optical fibre cable (EWZ0007)
* not available at Lenze; for list of suppliers please see the online documentation (
Show/Hide Bookmarks