Weidmuller AMS400A - Universal interface device Benutzerhandbuch

Seite 28

Advertising
background image

28

PowerSupplyRequirements

Check the power supply against the model number before applying

power to the instrument. Units must be used with a suitable mains
Power Supply, ratings are as follows:

Voltage Range

Nominal Voltage

Power

Frequency

100 – 132 V AC

110 V AC

6 VA

47-63 Hz

200 – 264 V AC

240 V AC

6 VA

47-63 Hz

24 V DC*

24 V DC ±10 %

6 W (at 24 V DC)

-

Installationconfigurations

A fully configured AMS400A can be installed in three ways:

• ‘AA’ - between analogue controlling equipment and analogue

control element

• ‘dA’ - between digital controlling equipment and analogue control

element

• ‘dd’ - between digital controlling equipment and digital control

element

Analogue means standard current/voltage signals, e.g., 4-20 mA loop.
Digital means two digital lines (one for ‘up’ and one for ‘down’) which

can be voltage pulse, solid state switch or relay contact closures.

The three installation configurations are described in detail under

separate headings below.

Note: for connection to analogue control devices the AMS400A must

be fitted with the analogue output option (/AO). For digital control
devices, the AMS400A must be fitted with the relay output option
(/RO).

Advertising