•AnalogueInputtypeSelection/Calibration

Inputtypeselection

The AMS400A series instruments are factory calibrated to the range

ordered. If you have the necessary equipment, you can change the
input type and adjustment range by changing components according
to the table below. The Instrument will need recalibration.

InputAdjustmentRange

R1

R2

R3

R4

0-8 mA thru 0-24 mA

36R

68K

Omit

120K

0-4 V DC thru 0-12 V DC

Omit

1M

75K

120K

0-1 V DC

Omit

68K

Omit

82K

AnalogueInputCalibration

Equipmentrequirements
• A suitable current or voltage source

TerminalConnectionsforinputcalibration

CalibrationStage

Signaltype

Terminal

Analogue Inputs

Signal source (+)

11

Signal source (−)

12

Procedure

Note: Allow 1 mins of powered operation before calibration.