Weidmuller AMS400A - Universal interface device Benutzerhandbuch

Seite 29

Advertising
background image

2

Connections

For effective protection from electromagnetic noise, all signal cables

must be shielded, or located on conductive trays or in conduits.

Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,

tighten to 4. lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).

Terminal

Signal

1

Neutral / −

Power supply

2

Live / +

3

Signal +

Analogue output

4

Signal −

5

0V

Status Outputs

6

AUTO/MAN

7

Handover Status

8

Common

Digital Input

9

Increment

10

Decrement

11

Signal +

Analogue Input

12

Signal −

13

Normally Closed

Increment
Relay Output

14

Common

15

Normally Open

16

Normally Closed

Decrement
Relay Output

17

Common

18

Normally Open

Advertising