Trip curve, Short circuit ratings – Rockwell Automation 193-EExx E1 Plus Overload Relay Benutzerhandbuch

Seite 5

Advertising
background image

(5)

Múltiplo de FLA

Vielfache des FLA-Wertes

Multiple of FLA

Intensités pleine charge multiples

Class 10

Class 15

Class 20

Class 30

Trip Curve

HOT START
DEMARRAGE A CHAUD
WARMSTART
ARRANQUE EN CALIENTE

PARTIDA À QUENTE
AVVIAMENTO A CALDO

COLD START
DEMARRAGE A FROID
KALTSTART
ARRANQUE EN FRIO

PARTIDA À FRIO
AVVIAMENTO A FREDDO

Courbe de déclenchement
Auslösekurve
Curva del disparo

Curva de disparo
Curva di intervento

0.1

1

10

100

1000

1

8

0.1

1

10

100

1000

1

8

0.1

1

10

100

1000

1

8

0.1

1

10

100

1000

1

8

Intensités pleine charge multiples

Multiplo di Max amp.

Short Circuit Ratings

Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No. 14

Max. available fault

current (kA)

Max. voltage (V)

S.C.P.D.

ED1AB, ED1BB, EEAB,
EEBB

1

Suitable for use

with fuses only

ED1CB, ED1DB, ED1EB,
ED1ED, ED1FD
EECB, EEDB, EEEB, EEED,
EEFD, EEPB, EERB, EESB,
EETD

5

EEEE, EEFE, EEGE, EEUE,
EEVE

10

E1 Plus Cat. No.

Not resticted to

fusing only

193, 193S

600

Table 4 High Fault Short Circuit Ratings, using Fusing, per UL508 and CSA 22.2 No. 14

Contactor Cat. No.

Max. starter FLC

(A)

Max.available

fault current (kA) Max. voltage (V)

Max. UL Class J or CC
fuse, CSA HRCI-J (A)

ED1AB, EEAB

0.5

3

ED1BB, EEBB

1

6

100-C09

9

20

100-C12

12

20

100-C16

16

30

100-C23

23

40

100-C30

30

50

100-C37

37

50

100-C43

43

70

100-C60

60

80

100-C72

72

100

100-C85

85

150

E1 Plus Cat. No.

EEED, EEFD

ED1ED, ED1FD

EEEE, EEFE, EEGE

100

600

ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB

193

193-EEED or 193-EEFD with 100-C30, 100-C37 or 100-C43 contactor: 480V/65kA; 600V/30kA when protected by Allen-Bradley 140U-H6C3
followed by suffixes CB rated 50A max.

100-C09

Table 3 Short Circuit Ratings per EN 60947-4-1

Table 6 Fuse Selection Table Class gL/gG and Class aM Fusing

Prospective S.C.

current, Ir (kA)

Conditional S.C.

current, Iq (kA)

Max.
voltage (V)

S.C.P.D.

ED1AB, ED1BB, EEAB,
EEBB

1

Suitable for use

with fuses only

ED1CB, ED1DB, EECB,
EEDB, EEPB, EERB

1

ED1EB, EEEB, ED1ED,
ED1FD, EEED,
EEFD, EEEE, EEFE,
EESB, EETD

3

EEGE, EEUE, EEVE

5

E1 Plus Cat. No.

100

690

Not resticted to

fusing only

193,193S

Table 2 Type I and Type II Fuse Coordination with Bul. 100-C contactors per EN 60947-4-1

Contactor Cat. No. Max. starter FLC

(A)

Prospective S.C.

current, Ir (kA)

Conditional S.C.

current, Iq (kA)

Max. voltage

(V)

Type I Max. Class
J or CC fuse (A)

Type II Max. Class

J or CC fuse (A)

ED1AB, EEAB

0.5

3

3

ED1BB, EEBB

1

6

6

100-C09

9

20

15

100-C12

12

20

20

100-C16

16

30

30

100-C23

23

40

40

100-C09

9

20

15

100-C12

12

20

20

100-C16

16

30

30

100-C23

23

40

40

100-C30

30

50

50

100-C37

37

50

50

100-C43

43

70

70

100-C60

60

80

80

100-C72

72

100

100

100-C85

85

150

150

100-C60

60

80

80

100-C72

72

100

100

100-C85

85

150

150

EEED, EEFD

ED1ED, ED1FD

100-C09

193

E1 Plus Cat. No.

3

100

EEGE

600

3

3

5

ED1EB, EEEB

EEEE, EEFE

1

ED1CB, ED1DB, EECB,
EEDB

1

100-C97

97

150

150

Contactor

1500 rpm

Type

Rated

Type

Type

Thermal

Current

Setting

[kW]

[A]

[A]

[A]

0.06

0.24

Class aM

1

100-C09

193-ED1AB

0.10 - 0.50

0.09

0.33

Class aM

1

100-C09

193-ED1AB

0.10 - 0.50

0.12

0.43

Class aM

1

100-C09

193-ED1AB

0.10 - 0.50

0.18

0.61

Class aM

2

100-C09

193-ED1BB

0.20 - 1.0

0.25

0.8

Class aM

2

100-C09

193-ED1BB

0.20 - 1.0

0.37

1.1

Class aM

2

100-C09

193-ED1CB

1.0 - 5.0

0.55

1.5

Class aM

2

100-C09

193-ED1CB

1.0 - 5.0

0.75

1.9

Class aM

4

100-C09

193-ED1CB

1.0 - 5.0

1.1

2.7

Class aM

4

100-C09

193-ED1CB

1.0 - 5.0

1.5

3.5

Class aM

4

100-C09

193-ED1CB

1.0 - 5.0

2.2

5.0

Class aM

6

100-C09

193-ED1DB

3.2 - 16

3

6.6

Class aM

8

100-C09

193-ED1DB

3.2 - 16

4

8.5

Class aM

10

100-C09

193-ED1DB

3.2 - 16

5.5

11

Class aM

12

100-C12

193-ED1DB

3.2 - 16

7.5

15

Class aM

16

100-C16

193-ED1DB

3.2 - 16

11

22

Class aM

25

100-C30

193-EEFD

9 - 45

15

29

Class aM

32

100-C30

193-EEFD

9 - 45

18.5

36

Class aM

40

100-C37

193-EEFD

9 - 45

22

41

Class aM

50

100-C43

193-EEFD

9 - 45

30

56

Class aM

63

100-C60

193-EEGE

18 - 90

37

68

Class aM

80

100-C72

193-EEGE

18 - 90

45

81

Class aM

100

100-C85

193-EEGE

18 - 90

Recommended Fuse

ED/EE O/L Relay

Motor

Table 5 Overload relay only, High fault short circuit ratings per UL508 and CSA 22.2 No. 14

Max. available fault.

current (kA)

Max. voltage (V)

UL class RK1 fuse (A)

ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB
ED1ED, ED1FD, EEED,
EEFD

100

EEEE, EEFE, EEGE

Cat. No.

600

60

100

200

193

EEVE

Contactor

1500 rpm

Type

Rated

Type

Type

Thermal

Current

Setting

[kW]

[A]

[A]

[A]

0.06

0.24

Class gL/gG

2

100-C09

193-ED1AB

0.10 - 0.50

0.09

0.33

Class gL/gG

2

100-C09

193-ED1AB

0.10 - 0.50

0.12

0.43

Class gL/gG

2

100-C09

193-ED1AB

0.10 - 0.50

0.18

0.61

Class gL/gG

2

100-C09

193-ED1BB

0.20 - 1.0

0.25

0.8

Class gL/gG

4

100-C09

193-ED1BB

0.20 - 1.0

0.37

1.1

Class gL/gG

4

100-C09

193-ED1CB

1.0 - 5.0

0.55

1.5

Class gL/gG

6

100-C09

193-ED1CB

1.0 - 5.0

0.75

1.9

Class gL/gG

6

100-C09

193-ED1CB

1.0 - 5.0

1.1

2.7

Class gL/gG

10

100-C09

193-ED1CB

1.0 - 5.0

1.5

3.5

Class gL/gG

10

100-C09

193-ED1CB

1.0 - 5.0

2.2

5.0

Class gL/gG

16

100-C09

193-ED1DB

3.2 - 16

3

6.6

Class gL/gG

20

100-C09

193-ED1DB

3.2 - 16

4

8.5

Class gL/gG

25

100-C09

193-ED1DB

3.2 - 16

5.5

11

Class gL/gG

32

100-C12

193-ED1DB

3.2 - 16

7.5

15

Class gL/gG

40

100-C23

193-ED1DB

3.2 - 16

10

20

Class gL/gG

50

100-C30

193-EEED

5.4 - 27

11

22

Class gL/gG

63

100-C30

193-EEED

5.4 - 27

15

29

Class gL/gG

80

100-C30

193-EEFD

9 - 45

18.5

36

Class gL/gG

80

100-C37

193-EEFD

9 - 45

22

41

Class gL/gG

100

100-C43

193-EEFD

9 - 45

30

56

Class gL/gG

125

100-C60

193-EEGE

18 - 90

37

68

Class gL/gG

160

100-C72

193-EEGE

18 - 90

45

81

Class gL/gG

160

100-C85

193-EEGE

18 - 90

Recommended Fuse

ED/EE O/L Relay

Motor

41053-358-01
DIR 41053-358 (Version 09)