Trip curve, Short circuit ratings – Rockwell Automation 193-EExx E1 Plus Overload Relay Benutzerhandbuch
Seite 5

(5)
Múltiplo de FLA
Vielfache des FLA-Wertes
Multiple of FLA
Intensités pleine charge multiples
Class 10
Class 15
Class 20
Class 30
Trip Curve
HOT START
DEMARRAGE A CHAUD
WARMSTART
ARRANQUE EN CALIENTE
PARTIDA À QUENTE
AVVIAMENTO A CALDO
COLD START
DEMARRAGE A FROID
KALTSTART
ARRANQUE EN FRIO
PARTIDA À FRIO
AVVIAMENTO A FREDDO
Courbe de déclenchement
Auslösekurve
Curva del disparo
Curva de disparo
Curva di intervento
0.1
1
10
100
1000
1
8
0.1
1
10
100
1000
1
8
0.1
1
10
100
1000
1
8
0.1
1
10
100
1000
1
8
Intensités pleine charge multiples
Multiplo di Max amp.
Short Circuit Ratings
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No. 14
Max. available fault
current (kA)
Max. voltage (V)
S.C.P.D.
ED1AB, ED1BB, EEAB,
EEBB
1
Suitable for use
with fuses only
ED1CB, ED1DB, ED1EB,
ED1ED, ED1FD
EECB, EEDB, EEEB, EEED,
EEFD, EEPB, EERB, EESB,
EETD
5
EEEE, EEFE, EEGE, EEUE,
EEVE
10
E1 Plus Cat. No.
Not resticted to
fusing only
193, 193S
600
Table 4 High Fault Short Circuit Ratings, using Fusing, per UL508 and CSA 22.2 No. 14
Contactor Cat. No.
Max. starter FLC
(A)
Max.available
fault current (kA) Max. voltage (V)
Max. UL Class J or CC
fuse, CSA HRCI-J (A)
ED1AB, EEAB
0.5
3
ED1BB, EEBB
1
6
100-C09
9
20
100-C12
12
20
100-C16
16
30
100-C23
23
40
100-C30
30
50
100-C37
37
50
100-C43
43
70
100-C60
60
80
100-C72
72
100
100-C85
85
150
E1 Plus Cat. No.
EEED, EEFD
ED1ED, ED1FD
EEEE, EEFE, EEGE
100
600
ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB
193
193-EEED or 193-EEFD with 100-C30, 100-C37 or 100-C43 contactor: 480V/65kA; 600V/30kA when protected by Allen-Bradley 140U-H6C3
followed by suffixes CB rated 50A max.
100-C09
Table 3 Short Circuit Ratings per EN 60947-4-1
Table 6 Fuse Selection Table Class gL/gG and Class aM Fusing
Prospective S.C.
current, Ir (kA)
Conditional S.C.
current, Iq (kA)
Max.
voltage (V)
S.C.P.D.
ED1AB, ED1BB, EEAB,
EEBB
1
Suitable for use
with fuses only
ED1CB, ED1DB, EECB,
EEDB, EEPB, EERB
1
ED1EB, EEEB, ED1ED,
ED1FD, EEED,
EEFD, EEEE, EEFE,
EESB, EETD
3
EEGE, EEUE, EEVE
5
E1 Plus Cat. No.
100
690
Not resticted to
fusing only
193,193S
Table 2 Type I and Type II Fuse Coordination with Bul. 100-C contactors per EN 60947-4-1
Contactor Cat. No. Max. starter FLC
(A)
Prospective S.C.
current, Ir (kA)
Conditional S.C.
current, Iq (kA)
Max. voltage
(V)
Type I Max. Class
J or CC fuse (A)
Type II Max. Class
J or CC fuse (A)
ED1AB, EEAB
0.5
3
3
ED1BB, EEBB
1
6
6
100-C09
9
20
15
100-C12
12
20
20
100-C16
16
30
30
100-C23
23
40
40
100-C09
9
20
15
100-C12
12
20
20
100-C16
16
30
30
100-C23
23
40
40
100-C30
30
50
50
100-C37
37
50
50
100-C43
43
70
70
100-C60
60
80
80
100-C72
72
100
100
100-C85
85
150
150
100-C60
60
80
80
100-C72
72
100
100
100-C85
85
150
150
EEED, EEFD
ED1ED, ED1FD
100-C09
193
E1 Plus Cat. No.
3
100
EEGE
600
3
3
5
ED1EB, EEEB
EEEE, EEFE
1
ED1CB, ED1DB, EECB,
EEDB
1
100-C97
97
150
150
Contactor
1500 rpm
Type
Rated
Type
Type
Thermal
Current
Setting
[kW]
[A]
[A]
[A]
0.06
0.24
Class aM
1
100-C09
193-ED1AB
0.10 - 0.50
0.09
0.33
Class aM
1
100-C09
193-ED1AB
0.10 - 0.50
0.12
0.43
Class aM
1
100-C09
193-ED1AB
0.10 - 0.50
0.18
0.61
Class aM
2
100-C09
193-ED1BB
0.20 - 1.0
0.25
0.8
Class aM
2
100-C09
193-ED1BB
0.20 - 1.0
0.37
1.1
Class aM
2
100-C09
193-ED1CB
1.0 - 5.0
0.55
1.5
Class aM
2
100-C09
193-ED1CB
1.0 - 5.0
0.75
1.9
Class aM
4
100-C09
193-ED1CB
1.0 - 5.0
1.1
2.7
Class aM
4
100-C09
193-ED1CB
1.0 - 5.0
1.5
3.5
Class aM
4
100-C09
193-ED1CB
1.0 - 5.0
2.2
5.0
Class aM
6
100-C09
193-ED1DB
3.2 - 16
3
6.6
Class aM
8
100-C09
193-ED1DB
3.2 - 16
4
8.5
Class aM
10
100-C09
193-ED1DB
3.2 - 16
5.5
11
Class aM
12
100-C12
193-ED1DB
3.2 - 16
7.5
15
Class aM
16
100-C16
193-ED1DB
3.2 - 16
11
22
Class aM
25
100-C30
193-EEFD
9 - 45
15
29
Class aM
32
100-C30
193-EEFD
9 - 45
18.5
36
Class aM
40
100-C37
193-EEFD
9 - 45
22
41
Class aM
50
100-C43
193-EEFD
9 - 45
30
56
Class aM
63
100-C60
193-EEGE
18 - 90
37
68
Class aM
80
100-C72
193-EEGE
18 - 90
45
81
Class aM
100
100-C85
193-EEGE
18 - 90
Recommended Fuse
ED/EE O/L Relay
Motor
Table 5 Overload relay only, High fault short circuit ratings per UL508 and CSA 22.2 No. 14
Max. available fault.
current (kA)
Max. voltage (V)
UL class RK1 fuse (A)
ED1CB, ED1DB, ED1EB,
EECB, EEDB, EEEB
ED1ED, ED1FD, EEED,
EEFD
100
EEEE, EEFE, EEGE
Cat. No.
600
60
100
200
193
EEVE
Contactor
1500 rpm
Type
Rated
Type
Type
Thermal
Current
Setting
[kW]
[A]
[A]
[A]
0.06
0.24
Class gL/gG
2
100-C09
193-ED1AB
0.10 - 0.50
0.09
0.33
Class gL/gG
2
100-C09
193-ED1AB
0.10 - 0.50
0.12
0.43
Class gL/gG
2
100-C09
193-ED1AB
0.10 - 0.50
0.18
0.61
Class gL/gG
2
100-C09
193-ED1BB
0.20 - 1.0
0.25
0.8
Class gL/gG
4
100-C09
193-ED1BB
0.20 - 1.0
0.37
1.1
Class gL/gG
4
100-C09
193-ED1CB
1.0 - 5.0
0.55
1.5
Class gL/gG
6
100-C09
193-ED1CB
1.0 - 5.0
0.75
1.9
Class gL/gG
6
100-C09
193-ED1CB
1.0 - 5.0
1.1
2.7
Class gL/gG
10
100-C09
193-ED1CB
1.0 - 5.0
1.5
3.5
Class gL/gG
10
100-C09
193-ED1CB
1.0 - 5.0
2.2
5.0
Class gL/gG
16
100-C09
193-ED1DB
3.2 - 16
3
6.6
Class gL/gG
20
100-C09
193-ED1DB
3.2 - 16
4
8.5
Class gL/gG
25
100-C09
193-ED1DB
3.2 - 16
5.5
11
Class gL/gG
32
100-C12
193-ED1DB
3.2 - 16
7.5
15
Class gL/gG
40
100-C23
193-ED1DB
3.2 - 16
10
20
Class gL/gG
50
100-C30
193-EEED
5.4 - 27
11
22
Class gL/gG
63
100-C30
193-EEED
5.4 - 27
15
29
Class gL/gG
80
100-C30
193-EEFD
9 - 45
18.5
36
Class gL/gG
80
100-C37
193-EEFD
9 - 45
22
41
Class gL/gG
100
100-C43
193-EEFD
9 - 45
30
56
Class gL/gG
125
100-C60
193-EEGE
18 - 90
37
68
Class gL/gG
160
100-C72
193-EEGE
18 - 90
45
81
Class gL/gG
160
100-C85
193-EEGE
18 - 90
Recommended Fuse
ED/EE O/L Relay
Motor
41053-358-01