Rockwell Automation 193-EExx E1 Plus Overload Relay Benutzerhandbuch

Seite 6

Advertising
background image

Table 7 High fault short circuit ratings, using Bul. 140M, circuit breakers, per UL508 and CSA 22.2 No.14

Table 8 High fault short circuit ratings, using Bul. 140U, circuit breakers, per UL508 and CSA 22.2 No.14

A

F

G

B

D

E

K

H

C

J

CONTACTOR CAT. NO.

E1 PLUS CAT. NO.

A

B

C

D

E

F

G

H

J

K

100-C09, -C12,

-C16, -C23

193-ED1_B, 193*-EE_B

mm

(in)

45

(1.76)

146.6

146.6

146.6

146.6

(5.77)

85.2

23.8

(.94)

23.8

(.94)

(3.35)

24.5

24.5

24.5

24.5

(.96)

13.9

13.9

13.9

(.55)

35

(1.38)

60

(2.36)

86.5

(3.40)

2

(.08)

4.5

(.17)

4.5

(.17)

4.5

(.17)

5.4

(.21)

4.5

(.17)

5.4

(.21)

100-C30, -C37

mm

(in)

45

(1.76)

(5.77)

101.2
(3.98)

101.2
(3.98)

101.2
(3.98)

(.96)

(.55)

35

(1.38)

60

(2.36)

104

(4.09)

104

(4.09)

104

(4.09)

2

(.08)

100-C43

mm

(in)

54

(2.12)

(5.77)

(.96)

18.4

(.74)

45

(1.77)

60

(2.36)

2

(.08)

100-C60, -C72, -C85, -C97

193*-EE_E

mm

(in)

72

(2.83)

192

(7.57)

120.4

120.4

(4.74)

29

(1.14)

55

(2.16)

100

(3.94)

126

(4.94)

2

(.08)

300-AO_, -BO_

193*-EE_D

193-ED1_D,

mm

(in)

45

(1.76)

(5.77)

(.96)

(.55)

35

(1.38)

60

(2.36)

2

(.08)

300-CO_

193*-EE_E

mm

(in)

72

(2.83)

192

(7.57)

(4.74)

29

(1.14)

55

(2.16)

100

(3.94)

126

(4.94)

2

(.08)

193*-EE_D

193-ED1_D,

At 480V

At 600Y/347 V

100-C30

30

65

30

140M-H8P-C30

30

100-C30

30

65

30

140M-H8P-C50

50

100-C37

37

65

30

140M-H8P-C50

50

100-C43

43

65

30

140M-H8P-C50

50

100-C60

60

65

30

140M-H8P-D10

100

100-C72

72

65

30

140M-H8P-D10

100

100-C85

85

65

30

140M-H8P-D10

100

Circuit Breaker Cat.

No.

Max. Circuit Breaker

Current (A)

EEEE, EEFE,

EEGE

193

ED1ED, ED1FD,

EEED, EEFD

Max. available fault current (kA)

E1 Plus Cat. No.

Contactor Cat.

No.

Max. starter

FLC (A)

At 480V

At 600V

100-C30

30

50

25

140U-H*C3-C50

50

100-C37

37

50

25

140U-H*C3-C50

50

100-C43

43

50

25

140U-H*C3-C50

50

100-C60

60

65

25

140U-H*C3-D11

110

100-C72

72

65

25

140U-H*C3-D11

110

100-C85

85

65

25

140U-H*C3-D11

110

Circuit Breaker Cat.

No.

Max. Circuit Breaker

Current (A)

193

ED1ED, ED1FD,

EEED, EEFD

EEEE, EEFE,

EEGE

E1 Plus Cat. No.

Contactor Cat.

No.

Max. starter

FLC (A)

Max. available fault current (kA)

Table 9 Group installation short circuit ratings

Catalog Nos. 193/592-EE and ED1 noted below have the following group installation short circuit ratings
when used with the specified contactors and branch circuit protection.

Overload Relay

Contactor

Max. Available
Fault Current

Max. Voltage

UL Fuse



193

-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
-ED1EB.


100-C09,
100-C12,
100-C16


5,000

480

Class RK5
60 Amp.

-EEAB, -EEBB, EECB,
-EEDB, -EEEB.

193

-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
-ED1EB.


100-C09,
100-C12,
100-C16



30,000

480


Class J
100 Amp

-EEAB, -EEBB, - EECB,
-EEDB, -EEEB.

41053-358-01
DIR 41053-358 (Version 09)

Printed in U.S.A.