Table 7 High fault short circuit ratings, using Bul. 140M, circuit breakers, per UL508 and CSA 22.2 No.14
Table 8 High fault short circuit ratings, using Bul. 140U, circuit breakers, per UL508 and CSA 22.2 No.14
A
F
G
B
D
E
K
H
C
J
CONTACTOR CAT. NO.
E1 PLUS CAT. NO.
A
B
C
D
E
F
G
H
J
K
100-C09, -C12,
-C16, -C23
193-ED1_B, 193*-EE_B
mm
(in)
45
(1.76)
146.6
146.6
146.6
146.6
(5.77)
85.2
23.8
(.94)
23.8
(.94)
(3.35)
24.5
24.5
24.5
24.5
(.96)
13.9
13.9
13.9
(.55)
35
(1.38)
60
(2.36)
86.5
(3.40)
2
(.08)
4.5
(.17)
4.5
(.17)
4.5
(.17)
5.4
(.21)
4.5
(.17)
5.4
(.21)
100-C30, -C37
mm
(in)
45
(1.76)
(5.77)
101.2
(3.98)
101.2
(3.98)
101.2
(3.98)
(.96)
(.55)
35
(1.38)
60
(2.36)
104
(4.09)
104
(4.09)
104
(4.09)
2
(.08)
100-C43
mm
(in)
54
(2.12)
(5.77)
(.96)
18.4
(.74)
45
(1.77)
60
(2.36)
2
(.08)
100-C60, -C72, -C85, -C97
193*-EE_E
mm
(in)
72
(2.83)
192
(7.57)
120.4
120.4
(4.74)
29
(1.14)
55
(2.16)
100
(3.94)
126
(4.94)
2
(.08)
300-AO_, -BO_
193*-EE_D
193-ED1_D,
mm
(in)
45
(1.76)
(5.77)
(.96)
(.55)
35
(1.38)
60
(2.36)
2
(.08)
300-CO_
193*-EE_E
mm
(in)
72
(2.83)
192
(7.57)
(4.74)
29
(1.14)
55
(2.16)
100
(3.94)
126
(4.94)
2
(.08)
193*-EE_D
193-ED1_D,
At 480V
At 600Y/347 V
100-C30
30
65
30
140M-H8P-C30
30
100-C30
30
65
30
140M-H8P-C50
50
100-C37
37
65
30
140M-H8P-C50
50
100-C43
43
65
30
140M-H8P-C50
50
100-C60
60
65
30
140M-H8P-D10
100
100-C72
72
65
30
140M-H8P-D10
100
100-C85
85
65
30
140M-H8P-D10
100
Circuit Breaker Cat.
No.
Max. Circuit Breaker
Current (A)
EEEE, EEFE,
EEGE
193
ED1ED, ED1FD,
EEED, EEFD
Max. available fault current (kA)
E1 Plus Cat. No.
Contactor Cat.
No.
Max. starter
FLC (A)
At 480V
At 600V
100-C30
30
50
25
140U-H*C3-C50
50
100-C37
37
50
25
140U-H*C3-C50
50
100-C43
43
50
25
140U-H*C3-C50
50
100-C60
60
65
25
140U-H*C3-D11
110
100-C72
72
65
25
140U-H*C3-D11
110
100-C85
85
65
25
140U-H*C3-D11
110
Circuit Breaker Cat.
No.
Max. Circuit Breaker
Current (A)
193
ED1ED, ED1FD,
EEED, EEFD
EEEE, EEFE,
EEGE
E1 Plus Cat. No.
Contactor Cat.
No.
Max. starter
FLC (A)
Max. available fault current (kA)
Table 9 Group installation short circuit ratings
Catalog Nos. 193/592-EE and ED1 noted below have the following group installation short circuit ratings
when used with the specified contactors and branch circuit protection.
Overload Relay
Contactor
Max. Available
Fault Current
Max. Voltage
UL Fuse
193
-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
-ED1EB.
100-C09,
100-C12,
100-C16
5,000
480
Class RK5
60 Amp.
-EEAB, -EEBB, EECB,
-EEDB, -EEEB.
193
-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
-ED1EB.
100-C09,
100-C12,
100-C16
30,000
480
Class J
100 Amp
-EEAB, -EEBB, - EECB,
-EEDB, -EEEB.
41053-358-01
DIR 41053-358 (Version 09)
Printed in U.S.A.