Setup menu

7 · MultiPower-6

Configuration settings

Delay until the first »Power Out« socket is active

After you turn on the central power supply, the first

Power Out

becomes active after a

delay of 0.7 seconds (

Power Start Delay

).

You can decrease or increase the delay by entering values between 0.0 and 10.0 sec-

onds (standard: 0.7 seconds).

How to adjust the delay until the first »Power Out« socket is active:
1. Start the terminal emulator.

2. Load the connection settings of the setup menu and establish the connection.

3. Press

R

within the terminal emulator.

4. Use the

Arrow

or

Arrow

keys to select

Power Start Delay

.

5. Use the

Arrow

or

Arrow

keys to decrease or increase the adjusted value.

6. Press

S

to save your settings.

Delay until further »Power Out« sockets are active

Following the first

Power Out

socket,all other sockets become successively active with a

delay of 0.1 seconds.

You can decrease or increase the delay by entering values between 0.0 and 2.0 sec-

onds (standard: 0.1 seconds).

How to adjust the delay until further sockets are enabled:
1. Start the terminal emulator.

2. Load the connection settings of the setup menu and establish the connection.

3. Press

R

within the terminal emulator.

4. Use the

Arrow

or

Arrow

keys to select

Power Channel Delay

.

5. Use the

Arrow

or

Arrow

keys to decrease or increase the adjusted value.

6. Press

S

to save your settings.