Electrical connection – WIKA DIH62 Benutzerhandbuch

Seite 19

Advertising
background image

WIKA operating instructions models DIH50, DIH52, DIH62

19

GB

14008548.02 03/2012 GB/D

Note:

Fixed wires as well as flexible wires with end splices are inserted directly into the terminal

openings. In the case of flexible wires without end splice, press with a slotted screwdriver

the terminal to release the terminal opening. By loosening the slotted screwdriver, the

terminals are closed again.

Check the correct fit by slight pulling.

Connect the screen to the internal earth terminal and the external earth terminal to the

equipotential bonding.

Put on the display and operation module and turn slightly to the right.

Tighten the cable gland and mount the case cover.

Note:

The terminal block is pluggable and can be pulled off from the electronics.

To do so, lift the terminal block using a small screwdriver and pull it out.

When plugging it again, it must engage with an audible click.

CAUTION!

When connecting an EN/IEC certified transmitter, please observe the

corresponding operating instructions and the requirements relating to the

transmitter.

7. Electrical connection

1 Connection of the transmitter: Connect the positive pole of the transmitter to the terminal marked with

⊕ (1) and the negative pole of the transmitter to the terminal marked with ⊖ (2).

2 Connection of the voltage supply: Connect the positive pole of the power supply to the terminal

marked with ⊕ (3) and the negative pole of the power supply to the terminal marked with ⊖ (4).

3 Connection of the display module: Put the display module connector accurately (coded!) on the

mating connector and press it down.

Transmitter

Voltage supply

Not Ex area

Ex area

Advertising