WIKA operating instructions models DIH50, DIH52, DIH62

GB

14008548.02 03/2012 GB/D

Installation in safe area

- The digital indicator for current loops model DIHxx-B must be mounted inside

a housing providing as a minimum ingress protection IP 20 in accordance with

IEC 60529.

- Wiring inside this housing shall be executed in accordance with section 6.3.11 and

7.6.e of the IEC 60079-11.

- Terminals or connectors for the intrinsically safe circuits shall be arranged in

accordance with clause 6.2.1 or 6.2.2 of IEC 60079-11 respectively.

9.3 Specific conditions for safe use of models DIH50-I, DIH52-I, DIH62-I (aluminium,

stainless steel)

Installation in areas requiring EPL Gb protection level equipment

(device marking Ex ia IIC T4/T5/T6 (Ga) Gb):

- Due to application, the digital indicator for current loops model DIHxx-B shall be

mounted inside a housing, suitable for installation in areas requiring EPL Gb equipment

providing as a minimum degree of ingress protection IP 20 in accordance with

IEC 60529.

- Wiring inside this housing shall be executed in accordance with section 6.3.11 and

7.6.e of the IEC 60079-11.

- Terminals or connectors for the intrinsically safe circuits shall be arranged according to

clause 6.2.1 or 6.2.2 of IEC 60079-11:2006 respectively.

Installation in areas requiring EPL Ga protection level equipment

(device marking Ex ia IIC T4/T5/T6 Ga):

- Due to application, the digital indicator for current loops model DIHxx-B shall be

mounted inside a housing, suitable for installation in areas requiring EPL Ga equipment

providing as a minimum degree of protection IP 54 according to IEC 60529 and

wherein electrostatic charge effects are excluded.

- Wiring inside this housing shall be executed in accordance with section 6.3.11 and

7.6.e of the IEC 60079-11.

- Terminals or connectors for the intrinsically safe circuits shall be arranged in

accordance with clause 6.2.1 or 6.2.2 of IEC 60079-11 respectively.

Installation in areas requiring EPL Db, Da protection level equipment

(device marking Ex ia IIIC T120 °C Da or 2D Ex ia IIIC T120 °C (Da) Db):

- Due to application, the digital indicator for current loops model DIHxx-B shall be

mounted inside a housing, suitable for installation in areas requiring EPL Db or Da

equipment providing as a minimum ingress protection IP 6x in accordance with

IEC 60529.

- Wiring inside this housing shall be executed in accordance with section 6.2.4 and 7.6.e

of the IEC 61241-11.

- Terminals or connectors for the intrinsically safe circuits shall be arranged in

accordance with section 6.3.1 or 6.3.2 of IEC 61241-11 respectively.

9. Information on mounting and operation in hazardous areas