WIKA operating instructions models DIH50, DIH52, DIH62

GB

14008548.02 03/2012 GB/D

8.2 Main menu "Display"

Function

Factory setting

Unit

Setting the unit for the display of the digital indicator

Here, you can select a unit deviating from the unit of the measuring range of the

connected transmitter. The measured values are then converted automatically

into the deviating unit.

However, only units of the same unit group as the set unit of the measuring

range may be selected.
Setting range (according to unit groups):

- Electrical measurement parameters: V, mA, Ω

- Pressure: bar, mbar, PSI, hPa, kPa, mmH

2

O, mH

2

O, inHG

- Temperature: °C, °F, K

- Others: %, USER

mA

Unit lock

By activating the unit lock, the set display unit is locked to protect the unit against

modifications. The display shows the sign . Modifications of the measuring

range are converted automatically.

The unit lock only functions if the units of the measuring range and the display

originate from the same unit group.

When connecting a transmitter and its configuration via HART

®

with a unit of

another unit group, then the unit lock is deactivated. In this case, the display unit

is set according to the configured measuring range unit.
Setting range:

- not locked (UnLoC)

- locked (LoC)

UnLoC

Indication range format

Setting the decimal point for the indication range of the digital indicator
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000

0.000

Filter

Activation of the digital filter of the 1st order;
Setting range: 0 ... 10

0

Alarm

From this menu item it is possible to branch into the submenu 2 for the alarm

configuration by selecting SELECT.

-----

Min/Max memory

From this menu item it is possible to branch into the submenu 2 for the min./max.

memory by selecting SELECT.

-----

8. Menu guidance