Menu guidance – WIKA DIH62 Benutzerhandbuch
Seite 21

WIKA operating instructions models DIH50, DIH52, DIH62
21
GB
14008548.02 03/2012 GB/D
8.1 Main menu "Measurement"
Function
Factory setting
Unit
Setting the unit of the measuring range of the connected transmitter
Setting range:
mA → Ω → bar → mbar → PSI → hPa → kPa → mmH
2
O → mH
2
O → inHG → °C →
°F → K → % → USER → V
mA
Measuring range start
Setting of the start value of the measuring range of the connected transmitter
(e.g. -30 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
4,000
Measuring range end
Setting the end value of the measuring range of the connected transmitter
(e.g. 120 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
20,000
Measuring range format
Setting the decimal point for the measuring range of the connected transmitter.
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
0.000
Span (only DIH52, DIH62)
The current measured value is applied as max. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Zero point (only DIH52, DIH62)
The current measured value is applied as min. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Damping (only DIH52, DIH62)
Input damping for damping the measured value.
Setting range: 0.0 … 999
0.0
Adress (only DIH52, DIH62)
Setting the HART
®
address of the assigned transmitter in the multidrop mode;
for the standard current loop mode, this address must always be set to 0.
Setting range: 0 ... 15
0
8. Menu guidance