30

3 Setup program

3.7.7 Fine calibration

Extras

Fine calibration (or the icon from the toolbar) desig-

nates the adjustment of the output signal of a calibrated transmitter.
The signal can be adjusted within the range of ±0.2mA for current
output and ±0.1V for voltage output.

After calling up the function, the window “Fine calibration” appears:

h

Perform fine calibration by using the arrow buttons and click OK.

You can discard fine calibration with Cancel.

H

When performing fine calibration of the offset and range
end, make sure that the corresponding input signal is pres-
ent.

The fine calibration data will be overwritten at the next data
transfer to the transmitter. In this case, fine calibration has
to be repeated.